- Manufacturer and part number on the existing component
- Door or operator model, plus size and finish where applicable
- Mounting style, handedness, and electrical specifications when relevant
Arrow AL500F-36 – Fire-Rated Alarmed Rim Exit Device | 36" | 103 dB Alarm
Replacement part details
The part number updates with your selected option. Confirm the size, finish, and configuration before ordering.
Check the specifications below for compatibility, then confirm your original part number and equipment details before ordering. Contact our parts team if you need help.
Arrow AL500F-36 – Fire-Rated Alarmed Rim Exit Device | 36" | 103 dB Alarm
Arrow AL500F-36 – Fire-Rated Alarmed Rim Exit Device | 36" | 103 dB Alarm
$1,457.00
$910.63
/
Buying several replacement parts? Choose the quantity, add this item to your cart, and continue shopping parts.
Pickup available at NC Warehouse
Usually ready in 2-4 days
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
The Arrow AL500F-36 Fire-Rated Alarmed Rim Exit Device combines dependable mechanical emergency egress with an integrated audible alarm for commercial and institutional fire-door openings.
Featuring a 36-inch nominal pushbar, 103-decibel pulsating alarm, 9V battery-powered electronics, guarded stainless steel deadlatch, and flashing LED status indicators, the AL500F-36 provides monitored exit operation while maintaining the positive latching required for properly approved fire-door assemblies.
Part of the Arrow AL500 Series, this fire-rated model is intended for outward-swinging doors measuring 32-1/4" to 36" wide.
When the alarm is armed, pressing the interior push rail immediately retracts the latchbolt, allowing occupants to exit. Simultaneously, the integrated horn activates to alert facility personnel to exit activity.
The standard alarm cycle lasts approximately two minutes before the horn automatically resets. A flashing red LED continues to identify the previous alarm violation until cleared by authorized key operation.
The AL500F-36 uses a 9V alkaline battery for its standard alarm functions, eliminating the need for a permanent external electrical connection.
Its microprocessor-controlled electronics offer adjustable alarm durations, selectable arming periods, and low-battery notification.
Unlike the standard non-fire-rated AL500-36, the AL500F-36 does not provide mechanical dogging. The latch must remain capable of engaging properly when the door closes.
Available in multiple architectural finishes, including Satin Stainless Steel, Aluminum Painted, Dark Bronze Painted, Black Suede Powder Coat, and Red Painted, the AL500F-36 can be specified for compatible commercial door hardware schedules.
Important: Fire-rated installation requires a properly labeled device and a compatible approved fire-door assembly. Verify the fire-rating classification and applicable hardware requirements before installation.
Key Features and Benefits
Fire-Rated Exit Hardware Configuration
-
Manufacturer-designated fire-rated model.
-
Designed for approved commercial fire-door applications.
-
Maintains mechanical panic exit operation.
-
Guarded rim latch provides positive latching.
-
No mechanical dogging or latch hold-down.
-
Suitable for properly specified fire-rated door assemblies.
-
Installation must comply with applicable NFPA 80 and fire-door requirements.
Integrated 103 dB Exit Alarm
-
Powerful 103-decibel pulsating horn measured at 8 feet.
-
Activates immediately when the armed push rail is depressed.
-
Provides an audible warning of exit activity.
-
Microprocessor-controlled alarm electronics.
-
Standard two-minute audible alarm cycle.
-
Adjustable alarm duration.
-
Continuous alarm option.
36-Inch Commercial Exit Device
-
Nominal 36-inch pushbar configuration.
-
Designed for 32-1/4" to 36" door widths.
-
Suitable for compatible outward-swinging commercial doors.
-
Surface-mounted rim latching.
-
No vertical rods required.
-
Interior pushbar provides immediate emergency egress.
9V Battery-Powered Alarm
-
Standard operation uses a 9V alkaline battery.
-
No permanent external power wiring required.
-
Convenient for compatible retrofit applications.
-
Battery-powered horn and status indicators.
-
Low-battery audible notification.
-
Replaceable battery.
Guarded Stainless Steel Deadlatch
-
Tamper-resistant guarded latch construction.
-
Stainless steel deadlatching bolt.
-
3/4-inch latchbolt throw.
-
Designed for reliable mechanical latching.
-
Helps maintain the closed and latched condition required by approved fire-door assemblies.
Three LED Status Indicators
Green LED – Armed
-
Indicates the alarm system is armed.
-
Flashes periodically during normal monitoring.
Yellow LED – Arming
-
Indicates the selected arming or passage period.
-
Signals that the alarm is transitioning into its armed state.
Red LED – Alarm Violation
-
Indicates an alarm activation.
-
Continues flashing after the programmed audible cycle.
-
Requires authorized key operation to clear the violation indication.
Adjustable Alarm Duration
Field-selectable alarm options include:
-
2-minute alarm
-
5-minute alarm
-
10-minute alarm
-
Continuous alarm until authorized reset
The factory-default audible alarm duration is two minutes.
Adjustable Arming and Passage Timing
Available settings include:
-
7 seconds
-
10 seconds
-
15 seconds
-
20 seconds
These settings control the electronic alarm's arming sequence. They do not delay the physical release of the exit door.
Automatic Alarm Reset
-
Standard audible alarm resets after the programmed cycle.
-
Factory-default reset interval is two minutes.
-
Red violation indicator remains active until keyed reset.
-
Automatic rearming functionality is available through the device's electronic controls.
Interior Key Control
-
Accepts a 1-1/8" mortise cylinder.
-
Requires a 001 cam.
-
Provides authorized alarm arming and disarming.
-
Interior cylinder is purchased separately.
-
Compatible interchangeable-core housing options may be available.
Multiple Architectural Finishes
| Finish Code | Description |
|---|---|
| 630 | Satin Stainless Steel |
| 689 | Aluminum Painted |
| 690 | Dark Bronze Painted |
| BSP | Black Suede Powder Coat |
| RD | Red Painted |
Available finished and handed combinations should be confirmed with the supplier.
Handing Options
-
Left Hand Reverse (LHR / LR)
-
Right Hand Reverse (RHR / RR)
Specify the correct handing for the opening.
Technical Specifications
| Specification | Details |
|---|---|
| Manufacturer | Arrow Lock & Door Hardware |
| Parent Company | ASSA ABLOY |
| Series | AL500 |
| Model | AL500F-36 |
| Product Type | Fire-Rated Alarmed Rim Exit Device |
| Nominal Size | 36" |
| Door Width Range | 32-1/4"–36" |
| Standard Door Thickness | 1-3/4" |
| Door Swing | Outward |
| Mounting | Surface-Mounted Rim |
| Alarm Output | 103 dB at 8 Feet |
| Alarm Type | Pulsating Audible Horn |
| Power Source | 9V Alkaline Battery |
| Alarm Electronics | Microprocessor Controlled |
| Standard Alarm Cycle | 2 Minutes |
| Adjustable Alarm Duration | 2, 5, 10 Minutes or Continuous |
| Arming/Passage Timing | 7, 10, 15 or 20 Seconds |
| LED Indicators | Green, Yellow and Red |
| Low-Battery Alert | Yes |
| Latch Type | Guarded Rim Deadlatch |
| Latchbolt Material | Stainless Steel |
| Latchbolt Throw | 3/4" |
| Rail Monitoring | Standard Internal Feature |
| Mechanical Dogging | No |
| Interior Arming Cylinder | 1-1/8" Mortise |
| Cylinder Cam | 001 |
| Cylinder Included | No |
| Exterior Trim | Sold Separately |
| Handing | LHR / RHR |
| Finishes | 630, 689, 690, BSP, RD |
| Fire-Rated | Yes, Subject to Exact Listing |
| Standard Version | AL500-36 |
| Selling Unit | Each |
How the Arrow AL500F-36 Works
1. Alarm Armed
Authorized personnel operate the interior mortise cylinder to arm the alarm system.
2. Arming Period
The yellow LED flashes during the programmed arming interval.
3. Armed Status
The device enters its armed state, indicated by periodic green LED flashes.
4. Pushbar Activation
An occupant depresses the horizontal exit pushbar.
5. Immediate Door Release
The rim latch retracts, allowing the door to open without delay.
6. Alarm Activation
The 103 dB horn sounds and the red violation indicator flashes.
7. Automatic Alarm Reset
After the programmed alarm period, the audible alarm stops unless continuous operation is selected.
8. Visual Violation Indication
The red LED continues indicating the previous alarm event until an authorized key reset.
9. Door Relatching
When the compatible self-closing fire door returns to its closed position, the latch engages the approved strike.
10. Battery Monitoring
An intermittent chirp alerts maintenance personnel when the battery requires replacement.
Recommended Commercial Applications
Commercial Office Buildings
-
Approved fire-rated service exits
-
Fire-rated corridor openings
-
Monitored building exits
-
Designated emergency egress doors
Schools and Universities
-
Approved fire-rated emergency exits
-
Institutional corridor openings
-
Maintenance facility exit doors
-
Security-monitored exits
Hospitals and Healthcare Facilities
-
Approved fire-door openings
-
Monitored support-area exits
-
Service corridor doors
-
Institutional egress openings
Warehouses and Distribution Centers
-
Fire-rated personnel exits
-
Warehouse fire-door openings
-
Monitored emergency exits
-
Industrial service openings
Government and Institutional Facilities
-
Fire-rated corridor doors
-
Monitored exit openings
-
Municipal building exits
-
Facility service doors
All applications must satisfy the fire rating and egress requirements of the complete door assembly.
Compatible Exterior Trim and Accessories
Arrow AL500 Series accessory selections include:
Lever Trim
-
SRX01 – Passage
-
SRX82 – Storeroom
-
SRX87 – Classroom
Knob Trim
-
BD01 / TA01 – Passage
-
BD12 / TA12 – Storeroom
-
BD17 / TA17 – Classroom
Plate Trim
-
PT01 – Passage
-
PT02 – Dummy Pull
-
PT03 – Classroom
Additional Accessories
-
MC61-004 – Mortise cylinder for interior alarm operation
-
16CR-27X004 – Interchangeable-core cylinder housing
-
S38 – Single-door strike
-
S36 – Double-door strike
-
FS54 – Through-bolt hardware
Important: For fire-rated installations, verify that the selected trim, strike, cylinder configuration, and mounting hardware are approved for the complete fire-door assembly.
Standard Package Information
The AL500F-36 device configuration incorporates:
-
Fire-rated rim exit device assembly
-
Horizontal panic push rail
-
Guarded mechanical rim latch
-
Alarm-control electronics
-
Integrated audible horn
-
Status LED indicators
-
Battery connection components
The interior arming/disarming mortise cylinder and exterior operating trim are sold separately.
Confirm battery inclusion, strike, and installation hardware with the supplier before fulfillment.
Installation Information
Professional installation is recommended for all fire-rated openings.
Step 1 – Verify Fire-Door Requirements
Confirm that the door, frame, closer, strike, and exit device are approved for the intended fire-rated assembly.
Step 2 – Verify Door Width
Ensure the door accommodates the AL500F-36 configuration.
Step 3 – Confirm Handing
Select the appropriate LHR or RHR device.
Step 4 – Prepare the Door
Use Arrow's AL500 Series installation template and approved fire-door preparation.
Step 5 – Install the Exit Device
Secure the rim chassis and push rail using the appropriate fasteners.
Step 6 – Install Approved Strike
Install and align the compatible fire-door strike.
Step 7 – Install Interior Mortise Cylinder
Fit the required 1-1/8" cylinder with 001 cam.
Step 8 – Install Alarm Battery
Connect the specified 9V alkaline battery.
Step 9 – Configure Alarm Settings
Select the required alarm duration and arming period.
Step 10 – Test the Complete Fire-Door Assembly
Verify immediate emergency egress, positive latching, proper self-closing, alarm operation, LED indicators, keyed reset, and compliance with the applicable fire-door listing.
Important Safety and Ordering Notes
-
This is the fire-rated AL500F-36 configuration.
-
It is not interchangeable with the standard AL500-36.
-
No mechanical dogging is permitted.
-
The latch must engage when the door closes.
-
A compatible approved fire-door closer is required as applicable.
-
The alarm does not delay emergency egress.
-
Select the correct finish and handing.
-
The interior arming cylinder is sold separately.
-
Exterior operating trim is sold separately.
-
Verify the exact fire-exit hardware listing and assembly rating.
-
Follow NFPA 80, applicable building codes, and manufacturer installation instructions.
Why Choose the Arrow AL500F-36?
The Arrow AL500F-36 Fire-Rated Alarmed Rim Exit Device combines immediate emergency egress, positive mechanical latching, and electronic exit monitoring.
Its 103 dB alarm, 9V battery operation, guarded stainless steel latch, adjustable alarm settings, and fire-rated configuration make it suitable for properly approved commercial fire-door applications requiring monitored exit activity.
For commercial door contractors, locksmiths, security integrators, and facility maintenance departments, the Arrow AL500F-36 provides a solution for combining fire-exit hardware with audible exit monitoring.